Early last Tuesday there was a widespread power outage at work , which took out power to our machine rooms for about four hours. Most things came back up when the power was restored, but not everything. One of the things that had happened was that one of our rack PDUs had failed. Fixing this took a surprising amount of work.
We don't normally think about our PDUs very much. They sit there, acting as larger and often smarter versions of power bars, and just, well, work. But both power bars and PDUs can fail eventually, and in our environment rack PDUs tend to last long enough to reach that point. We may replace servers in the racks in our machine rooms, but we don't pull out and replace entire racks all that often. The result is that a rack's initial PDU is likely to stay in the rack until it fails.
(This isn't universal; there are plenty of places that install and remove entire racks at a time. If you're turning over an entire rack, you might replace the PDU at the same time you're replacing all of the rest of it. Whole rack replacement is certainly going to keep your wiring neater.)
A rack PDU failing not a great thing for the obvious reason; it's going to take out much or all of the servers in the rack unless you have dual power supplies on your servers, each connected to a separate PDU. For racks that have been there for a while and gone through a bunch of changes, often it will turn out to be hard to remove and replace the PDU. Maintaining access to remove PDUs is often not a priority either in placing racks in your machine room or in wiring things up, so it's easy for things to get awkward and encrusted. This was one of the things that happened with our failed PDU on last Tuesday; it took quite some work to extract and replace it.
(Some people might have pre-deployed spare PDUs in each rack, but we don't. And if those spare PDUs are already connected to power and turned on, they too can fail over time.)
We're fortunate that we already had spare (smart) PDUs on hand, and we had also pre-configured a couple of them for emergency replacements. If we'd had to order a replacement PDU, things would obviously have been more of a problem. There are probably some research groups around here with their own racks who don't have a spare PDU, because it's an extra chunk of money for an unlikely or uncommon contingency, and they might choose to accept a rack being down for a while.